K-TURBO Blower communication driver is the driver to communicate with blower controller.
<Figure 1> is read setting example of K-TURBO Blower communication driver.
|  | 
| <Figure 1> Read setting example of K-TURBO Blower communication driver | 
Device part of <Figure 1> input Com Port(COM1), Baud Rate(19200), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively, according to controller.
K-TURBO Blower communication driver read schedule
Read schedule setting parameters are as follows:
1) Station – Don't care.
2) Read command – Don't care.
3) Read start address – Don't care.
4) Save start address for Communication Server – Saving start address of Communication Server.
5) Read Size – Fixed to 1.
Read schedule example)
READ, 0, 0, 0, 0, 1,
K-TURBO Blower communication driver save the readed data from controller.( refer to <Table 1> ) The controller send periodically data to communication driver.
<Table 1> is data saving address and contents for K-TURBO Blower communication driver.
| Data saving address | Contents | Range | 
| Start addr + 0 | pressure | 0 ~ 25599 ( real value = 0.00 ~ 255.99 ) | 
| Start addr + 1 | pressure difference at filter | |
| Start addr + 2 | operation pressure of setting BOV | |
| Start addr + 3 | moter RPM | 0 ~ 40000 | 
| Start addr + 4 | input motor current | 
 | 
| Start addr + 5 | target mortor RPM | 0 ~ 40000 | 
| Start addr + 6 | setting operation value | 
 | 
| Start addr + 7 | run stauts 1 00h = preparing 01h = READY 02h = FAULT 04h = unload run status 08h = load run status | eac bit status | 
| Start addr + 8 | run status 2 01h = Max Flow Mode 02h = Set Flow Mode 03h = Feedback Mode 04h = TBD | |
| Start addr + 9 | run status 3 01h = error of temperature sensor 02h = error of pressure sensor 04h = error of motor current 08h = error of motor rotation 10h = error of inverter 20h = over-heat status of inverter 40h = failure of start 80h = error of motor abnormal | |
| <Table 1> Data saving address and contents for K-TURBO Blower communication driver | ||
If you click the icon ![]() in protocol option part at 
<Figure 1>, you 
can see the help dialogue box such as <Figure 2>.
  in protocol option part at 
<Figure 1>, you 
can see the help dialogue box such as <Figure 2>.
|  | 
| <Figure 2> Help dialog box of K-TURBO Blower communication driver | 
You can control K-TURBO Blower controller by using 'writing settings'.
Digital Write
Digital write setting parameters are as follows:
1) PORT Port no. (0 ~ 255)
2) STATION Don't care.
3) ADDRESS Don't care.
4) Extra1 Write command.
A : setting of operation mode,
B : setting of operation command,
C : setting of BOV operation pressure,
D : setting of operation.
5) Extra2 Selection of feedback mode, operation load when A, D write command.
0 : Set Flow Mode, unload operation,
1 : Feedback Mode, load operation.
Write example 1)
PORT:0, station:0, ADDRESS:0000, Extra1: A, Extra2 : 0, Output value = Off
The setting parameter shown above is a setting example to Max Flow mode.
Write example 2)
PORT:0, station:0, ADDRESS:0000, Extra1: A, Extra2 : 0, Output value = On
The setting parameter shown above is a setting example to Set Flow mode.
Write example 3)
PORT:0, station:0, ADDRESS:0000, Extra1: A, Extra2 : 1, Output value = On
The setting parameter shown above is a setting example to Feedback mode.
Write example 4)
PORT:0, station:0, ADDRESS:0000, Extra1: D, Extra2 : 0, Output value = Off
The setting parameter shown above is stop setting example of Unload operation.
Write example 5)
PORT:0, station:0, ADDRESS:0000, Extra1: D, Extra2 : 0, Output value = On
The setting parameter shown above is start setting example of Unload operation.
Write example 6)
PORT:0, station:0, ADDRESS:0000, Extra1: D, Extra2 : 1, Output value = On
The setting parameter shown above is start setting example of Load operation.
Analog Write
Analog write setting parameters are as follows:
1) PORT Port no. (0 ~ 255)
2) STATION Don't care.
3) ADDRESS Don't care.
4) Extra1 Write command.
A : setting of operation mode,
B : setting of operation command,
C : setting of BOV operation pressure,
D : setting of operation.
5) Extra2 Don't care.
Write example 1)
PORT:0, station:0, ADDRESS:0000, Extra1: B, Extra2 : 0
The setting parameter shown above is setting example of operation command( output value = 0 ~ 255 ).
Write example 2)
PORT:0, station:0, ADDRESS:0000, Extra1: C, Extra2 : 0
The setting parameter shown above is setting example of BOV operation pressure( output value = 0 ~ 25599, real setting value = 0.00 ~ 255.99 ).